PRODUCT USE DESCRIPTION
01.It's necessary to keep the compressor without rubber plug as short as possible,it should be quickly loaded
into the refrigeration system within 10 minutes.(Suggest put off the plug on process tube first).
02.The return pipe of the refrigeration system must be connected with the suction pipe of the compressor,but
not with the process pipe of the compressor.Otherwise,the compressor will not work properly.
03.Operating capacitors should be fixed in the position of compressor accessories of refrigerators,and then
connected with PTC starters.
04.The grounding device of the compressor shall be permanently and reliably connected with the grounding
device of the refrigerating apparatus.
05.Compressor working and horizontal state inclination is not more than 5 degrees.
06.The working environment temperature of the compressor should not be higher than 43C.The condensation
pressure and peak pressure should not exceed the above values when running continuously at the highest
room temperature(43C).
07.In order to ensure the pressure balance of the system.the running interval of the compressor should not be
less than 5 minutes.
08.Compressors can not withstand high voltage or start and operate under vacuum conditions.Compressors
can not be used for system vacuum extraction.
09.Compressors should not be tilted or inverted during storage,transportation or installation,while avoiding
impact.
10.The storage period of compressor after leaving the factory should not exceed 6 months.If it exceeds 6
months,please check whether there is enough gas in the compressor and replenish it if necessary.
Special Requirement of R134a,R290 and R404A Compressor
01.The content of chlorine,water,paraffin and silicon should be strictly controlled in refrigeration system.
02.Organics with uncertain compatibility with R134a,R290 and R404A cannot be used in refrigeration systems.
03.Vacuum pumping and filling devices must be specially used for R134a,R290 and R404A.